On this page you will find information about what an OBIS code is and how to understand the values read from registers of an energy meter.

Physics OBIS codes index

OBIS code

OBIS code is a numerical code which represents the physical quantity measured by the meter. Let's look at the example.

1.8.0(158233.46*kWh)

It contains 3 elements: OBIS code 1.8.0, counter value 158233.46 and the unit kWh separated with specific characters. The OBIS codes corresponds to the type of measurement. For example, 1.8.0 corresponds to positive active energy consumed from the grid. What does that mean? This is the amount of active energy you consumed since your meter was installed (or its registers were reset).

The display of your meter will most likely show more readable values.

Why 1.8.0? It has been defined in the IEC62056-21 standard (as amended), in which the exact representation of OBIS codes must be represented. Most of the meters compatible with our device follow the concepts of this standard.

OBIS registers

obis-main

Summary codes

OBIS code represents how much
1.8.0 / 2.8.0 active energy has been consumed / returned to the grid
3.8.0 / 4.8.0 reactive energy has been received from / returned to the grid
5.8.0 / 7.8.0 inductive reactive energy has been received from / returned to the grid
6.8.0 / 8.8.0 capacitive reactive energy has been returned / received from the grid

We need two OBIS codes to represent the produced and consumed energy, because a meter counter counts forward only.

Tariff codes

OBIS code represents how much
1.8.1 - 1.8.4 active energy has been consumed in particular tariff zones
2.8.1 - 2.8.4 active energy has been returned to the grid in particular tariff zones

Index

Active energy

OBIS code description unit alias
1.8.0 Positive active energy, total kWh A+
1.8.1 Positive active energy in tariff I kWh A+ (T1)
1.8.2 Positive active energy in tariff II kWh A+ (T2)
1.8.3 Positive active energy in tariff III kWh A+ (T3)
1.8.4 Positive active energy in tariff IV kWh A+ (T4)
2.8.0 Negative active energy, total kWh A-
2.8.1 Negative active energy in tariff I kWh A- (T1)
2.8.2 Negative active energy in tariff II kWh A- (T2)
2.8.3 Negative active energy in tariff III kWh A- (T3)
2.8.4 Negative active energy in tariff IV kWh A- (T4)
15.8.0 / F.8.0 Absolute active energy, total kWh |A|
15.8.1 / F.8.1 Absolute active energy, total in tariff I kWh |A| (T1)
15.8.2 / F.8.2 Absolute active energy, total in tariff II kWh |A| (T2)
15.8.3 / F.8.3 Absolute active energy, total in tariff III kWh |A| (T3)
15.8.4 / F.8.4 Absolute active energy, total in tariff IV kWh |A| (T4)
21.8.0 Positive active energy in phase I, total kWh A+ (L1)
41.8.0 Positive active energy in phase II, total kWh A+ (L2)
61.8.0 Positive active energy in phase III, total kWh A+ (L3)
22.8.0 Negative active energy in phase I, total kWh A- (L1)
42.8.0 Negative active energy in phase II, total kWh A- (L2)
62.8.0 Negative active energy in phase III, total kWh A- (L3)
35.8.0 Absolute active energy in phase I, total kWh |A| (L1)
55.8.0 Absolute active energy in phase II, total kWh |A| (L2)
75.8.0 Absolute active energy in phase III, total kWh |A| (L3)

Active energy Tariff zone Phase

Reactive energy

OBIS code description unit alias
3.8.0 Positive reactive energy, total kvarh Q+
3.8.1 Positive reactive energy in tariff I kvarh Q+ (T1)
3.8.2 Positive reactive energy in tariff II kvarh Q+ (T2)
3.8.3 Positive reactive energy in tariff III kvarh Q+ (T3)
3.8.4 Positive reactive energy in tariff IV kvarh Q+ (T4)
4.8.0 Negative reactive energy, total kvarh Q-
4.8.1 Negative reactive energy in tariff I kvarh Q- (T1)
4.8.2 Negative reactive energy in tariff II kvarh Q- (T2)
4.8.3 Negative reactive energy in tariff III kvarh Q- (T3)
4.8.4 Negative reactive energy in tariff IV kvarh Q- (T4)
5.8.0 Reactive energy in I quadrant, total kvarh QL+
5.8.1 Reactive energy in I quadrant in tariff I kvarh QL+ (T1)
5.8.2 Reactive energy in I quadrant in tariff II kvarh QL+ (T2)
5.8.3 Reactive energy in I quadrant in tariff III kvarh QL+ (T3)
5.8.4 Reactive energy in I quadrant in tariff IV kvarh QL+ (T4)
6.8.0 Reactive energy in II quadrant, total kvarh QC+
6.8.1 Reactive energy in II quadrant in tariff I kvarh QC+ (T1)
6.8.2 Reactive energy in II quadrant in tariff II kvarh QC+ (T2)
6.8.3 Reactive energy in II quadrant in tariff III kvarh QC+ (T3)
6.8.4 Reactive energy in II quadrant in tariff IV kvarh QC+ (T4)
7.8.0 Reactive energy in III quadrant, total kvarh QL-
7.8.1 Reactive energy in III quadrant in tariff I kvarh QL- (T1)
7.8.2 Reactive energy in III quadrant in tariff II kvarh QL- (T2)
7.8.3 Reactive energy in III quadrant in tariff III kvarh QL- (T3)
7.8.4 Reactive energy in III quadrant in tariff IV kvarh QL- (T4)
8.8.0 Reactive energy in IV quadrant, total kvarh QC-
8.8.1 Reactive energy in IV quadrant in tariff I kvarh QC- (T1)
8.8.2 Reactive energy in IV quadrant in tariff II kvarh QC- (T2)
8.8.3 Reactive energy in IV quadrant in tariff III kvarh QC- (T3)
8.8.4 Reactive energy in IV quadrant in tariff IV kvarh QC- (T4)

Reactive energy Tariff zone Quadrant

Apparent energy

OBIS code description unit alias
9.8.0 Apparent energy, total kVAh S+
9.8.1 Apparent energy in tariff I kVAh S+ (T1)
9.8.2 Apparent energy in tariff II kVAh S+ (T2)
9.8.3 Apparent energy in tariff III kVAh S+ (T3)
9.8.4 Apparent energy in tariff IV kVAh S+ (T4)

Apparent energy Tariff zone

Power demand

OBIS code description unit alias
1.6.0 Positive active maximum demand, total kW
1.6.1 Positive active maximum demand in tariff I kW
1.6.2 Positive active maximum demand in tariff II kW
1.6.3 Positive active maximum demand in tariff III kW
1.6.4 Positive active maximum demand in tariff IV kW
2.6.0 Negative active maximum demand, total kW
2.6.1 Negative active maximum demand in tariff I kW
2.6.2 Negative active maximum demand in tariff II kW
2.6.3 Negative active maximum demand in tariff III kW
2.6.4 Negative active maximum demand in tariff IV kW
15.6.0 Absolute active maximum demand, total kW
15.6.1 Absolute active maximum demand in tariff I kW
15.6.2 Absolute active maximum demand in tariff II kW
15.6.3 Absolute active maximum demand in tariff III kW
15.6.4 Absolute active maximum demand in tariff IV kW
3.6.0 Positive reactive maximum demand, total kW
4.6.0 Negative reactive maximum demand, total kW
9.6.0 Apparent maximum demand, total kW

Power demand Tariff zone

Instantaneous power

OBIS code description unit alias
1.7.0 Positive active instantaneous power kW P+
21.7.0 Positive active instantaneous power in phase I kW P+ (L1)
41.7.0 Positive active instantaneous power in phase II kW P+ (L2)
61.7.0 Positive active instantaneous power in phase III kW P+ (L3)
2.7.0 Negative active instantaneous power kW P-
22.7.0 Negative active instantaneous power in phase I kW P- (L1)
42.7.0 Negative active instantaneous power in phase II kW P- (L2)
62.7.0 Negative active instantaneous power in phase III kW P- (L3)
15.7.0 Absolute active instantaneous power kW
35.7.0 Absolute active instantaneous power in phase I kW
55.7.0 Absolute active instantaneous power in phase II kW
75.7.0 Absolute active instantaneous power in phase III kW
3.7.0 Positive reactive instantaneous power kW P+
23.7.0 Positive reactive instantaneous power in phase I kW P+ (L1)
43.7.0 Positive reactive instantaneous power in phase II kW P+ (L2)
63.7.0 Positive reactive instantaneous power in phase III kW P+ (L3)
4.7.0 Negative reactive instantaneous power kW P-
24.7.0 Negative reactive instantaneous power in phase I kW P- (L1)
44.7.0 Negative reactive instantaneous power in phase II kW P- (L2)
64.7.0 Negative reactive instantaneous power in phase III kW P- (L3)
9.7.0 Apparent instantaneous power kW
29.7.0 Apparent instantaneous power in phase I kW
49.7.0 Apparent instantaneous power in phase II kW
69.7.0 Apparent instantaneous power in phase III kW

Active energy Instantaneous power Phase

Network parameters

OBIS code description unit alias
11.6.0 Maximal current A Imax
31.6.0 Maximal current in phase I A Imax (L1)
51.6.0 Maximal current in phase II A Imax (L2)
71.6.0 Maximal current in phase III A Imax (L3)
91.6.0 Maximal current in neutral A Imax (N)
11.7.0 Instantaneous current A I
31.7.0 Instantaneous current in phase I A I (L1)
51.7.0 Instantaneous current in phase II A I (L2)
71.7.0 Instantaneous current in phase III A I (L3)
91.7.0 Instantaneous current in neutral A I (N)
12.7.0 Instantaneous voltage V U
32.7.0 Instantaneous voltage in phase I V U (L1)
52.7.0 Instantaneous voltage in phase II V U (L2)
72.7.0 Instantaneous voltage in phase III V U (L3)
32.7.0 Instantaneous voltage in neutral V U (N)
14.7.0 Frequency of signal in the installation Hz f

Metadata

OBIS code description
0.0.0 Meter address (1)
0.0.1 Meter address (2)
0.2.0 Firmware version
0.2.2 Tariff code
0.9.1 Meter time
0.9.2 Meter date
0.9.4 Meter date & time
0.8.0 Peak power period
C.1.0 Meter serial number
C.90.1 Optical port serial number
F.F.0 Meter error register

Tariff Peak power

Special codes

OBIS code description example
S.1.1.2 Device battery status 2.76
S.1.1.4 Readout timestamp (real) 2020-11-19 10:45:02
S.1.1.6 Successful readouts since restart (e.g. battery replacement) 433
S.1.1.7 Failed readout attempts on 1-st/2-nd communication message 23/22
S.1.1.8 Meter communication parameters 3, 300
S.1.1.9 Temperature 24
S.1.1.10 Readout timestamp (corrected) 2020-11-19 10:45:00
S.1.1.12 Energy consumption (based on blink measurements) 10.44
S.1.1.16 Device status LAST_READOUT_INCORRECT

Clarifications

  • S.1.1.7: The device asks meter for data twice. First it asks for an identifier, then registers with OBIS values. That is why we may have failed readouts on two messages.
  • S.1.1.8: It is the infrared transmission power (3) and a baud rate used for the communication (300 bps).
  • S.1.1.12: Based on the blinks/usage ratio and number of blinks counted, we can calculate the estimated energy consumption.

OBIS codes supported

Check Compatible OBIS codes.